This product is covered by ACI's Five (5) Year Limited Warranty. Learn more
Product overview
100 Ohm (Three Wires) RTD, Probe Only, 12"
Application
- Roof Top Units
- Supply/Discharge Air/Return/Mixed/Exhaust Air Duct Temperature Sensing
- Immersion Temperature Sensors
- Replacement Temperature Sensors
Product specifications
Sensor Type | Sensor Curve:
Platinum RTD | PTC (Positive Temperature Coefficient)
Number Sensing Points:
One
Number Wires:
A/100-2W-PO-XX” Series and A/1K-2W-PO-XX Series: Two (Non-Polarity Sensitive)
A/1K-2W-PO-XX” Series and A/1K-3W-PO-XX Series: Three (Polarity Sensitive)
Sensor Output @ 0ºC (32ºF):
A/100-xW-PO Series: 100 Ohms nominal | A/1K-xW-PO Series: 1000 Ohms nominal
Sensor Accuracy:
+/- 0.06% Class A (Tolerance Formula: +/- ºC = (0.15ºC + (0.002 * |t|)) where |t| is the absolute value of Temperature above or below 0ºC in ºC)
-40ºC (-40ºF): +/- 0.23ºC (+/- 0.414ºF) | 0ºC (32ºF): +/- 0.15ºC (+/- 0.27ºF) | 200ºC (392ºF): +/- 0.55ºC (+/- 0.99ºF)
Din Standard | Temperature Coeffcient:
DIN EN 60751 (IEC 751) | 3850 ppm / ºC
Stability:
+/- 0.03% after 1000 Hours @ 300ºC (572ºF)
Response Time (63% Step Change):
8 Seconds nominal
Self-Heating | Maximum Operating Current:
100 Ohm RTD: 7 mW/ºC (Still Air) | 5 mA | 1K Ohm RTD: 4mW/ºC (Still Air) | 3 mA
Operating Temperature Range:
-40 to 200ºC (-40 to 392ºF)
Storage Temperature Range:
-40 to 85ºC (-40 to 185ºF)
Operating RH Range:
10 to 95% RH, non-condensing
Probe Material:
304 Stainless Steel
Standard Wire:
Lead Wire Insulation | Wire Rating:
Etched Teflon (PTFE) Colored Leads | MIL-W-16878/4 (Type E)
Operating Temperature Range:
-55°C (-67°F) to 200°C (392°F)
Conductor Material:
Silver Plated Copper
Rated Application:
Suitable for Indoor and Outdoor (wet) location. Oil, Moisture, Acids, Oils and Moisture Resistant
Lead Length | Conductor Size:
4”, 6” and 8” Probes: 14” (35.6 cm) | 12” and 18” Probes: 24” (61cm) | 22 AWG (0.65mm)
Plenum Wire:
Lead Wire Insulation | Wire Rating:
CL2P: FEP (Fluorinated Ethylene Propylene) | TYPE CL2P - TYPE CMP 22 AWG (UL), C(UL) FEP/FEP E130356 ROHS
Cable Operating Temperature Range:
CL2P: -80°C (-112°F) to 150°C (302°F)
Conductor Material:
CL2P: Tinned Copper
Rated Application:
CL2P: Suitable for Indoor and Outdoor (wet) locations. Oil, Gas, Sunlight, Abrasion Acid Resistant
Probe Material:
0.250" (6.35mm)
Product Weight:
4" = 0.028 lbs. (12.7g)
6" = 0.036 lbs. (16.3g)
8" = 0.044 lbs. (20g)
12" = 0.066 lbs. (29.9g)
18" = 0.09 lbs. (40.8g)
Agency Approvals:
CE, RoHS2, WEEE