Thermistors Probe Only

This product is covered by ACI's Five (5) Year Limited Warranty. Learn more

Product overview

10,000 Ohm (E1) Thermistor, Probe Only, 4", 10' Plenum Cable, NIST cert

Application

  • Roof Top Units
  • Supply/Discharge Air/Return/Mixed/Exhaust Air Duct Temperature Sensing
  • Immersion Temperature Sensors
  • Replacement Temperature Sensors

Product specifications

Sensor Type:
Thermistor
Sensor Curve:
Non-Linear NTC (Negative Temperature Coefficient)
Number Sensing Points:
One
Number Wires:
Two (Non-Polarity Sensitive)
Sensor Output @ 25ºC (77ºF):
A/1.8K: 1.8KΩ nominal | (Red/Yellow) A/3K: 3KΩ nominal | (White/Brown) A/AN (Type III): 10KΩ nominal | (White/White) A/AN-BC: 5.238KΩ nominal | (White/Yellow) A/CP (Type II): 10KΩ nominal | (White/Green) A/CSI: 10KΩ nominal | (Green/Yellow) A/10KS: 10KΩ nominal | (White/Blue) A/10K-E1: 10KΩ nominal | (Gray/Orange) A/20K: 20KΩ nominal | (Brown/Blue) A/50K: 50KΩ nominal | (Brown/Yellow) A/100KS: 100KΩ nominal | (Black/Yellow)
Accuracy 0-70ºC (32-158ºF):
+/-0.2ºC (+/-0.36ºF) except A/10K-E1 Series: +/- 0.3ºC (+/-0.54ºF) A/1.8K Series: +/- 0.5ºC @ 25ºC (77ºF) and (+/-1.0ºC) (+/-1.8ºF)
Stability:
Sensor Dependent; Contact ACI for more information on the sensor in question.
Platinum RTD Response Time (63% Step Change):
10 Seconds nominal
Power Dissipation Constant:
3 mW/ºC except A/1.8K Series: 1 mW/ºC | A/10K-E1 Series: 2 mW/ºC
Operating Temperature Range:
-40 to 150ºC (-40 to 302ºF)
Storage Temperature Range:
-40 to 85ºC (-40 to 185ºF)
Operating Humidity Range:
10 to 95% RH, non-condensing
Probe Material:
304 Stainless Steel
Standard Wire:
Lead Wire Insulation | Wire Rating:
Etched Teflon (PTFE) Colored Leads | MIL-W-16878/4 (Type E)
Operating Temperature Range:
-55°C (-67°F) to 200°C (392°F)
Conductor Material:
Silver Plated Copper
Rated Application:
Suitable for Indoor and Outdoor (wet) location. Oil, Moisture, Acids, Oils and Moisture Resistant
Lead Length | Conductor Size:
4”, 6” and 8” Probes: 14” (35.6 cm) | 12” and 18” Probes: 24” (61cm) | 22 AWG (0.65mm)
Plenum Wire:
Lead Wire Insulation | Wire Rating:
CL2P: FEP (Fluorinated Ethylene Propylene) | TYPE CL2P - TYPE CMP 22 AWG (UL), C(UL) FEP/FEP E130356 ROHS
Operating Temperature Range:
CL2P: -80°C (-112°F) to 150°C (302°F)
Conductor Material:
CL2P: Tinned Copper
Rated Application:
CL2P: Suitable for Indoor and Outdoor (wet) locations. Oil, Gas, Sunlight, Abrasion Acid Resistant
Probe Diameter:
0.250" (6.35mm)
Product Weight:
4" = 0.028 lbs. (12.7g) 6" = 0.036 lbs. (16.3g) 8" = 0.044 lbs. (20g) 12" = 0.066 lbs. (29.9g) 18” = 0.09 lbs. (40.8g)
Agency Approvals:
CE, RoHS2, WEEE