Nickel RTD No Box

This product is covered by ACI's Five (5) Year Limited Warranty. Learn more

Product overview

1,000 Ohm Nickel RTD, Duct, Without Box, 18", 10' Plenum Cable

Application

  • Roof Top Units
  • Monitoring Supply/Discharge/Return/Mixed Air Temperatures

Product specifications

Sensor Type | Sensor Curve:
Nickel RTD | PTC (Positive Temperature Coefficient)
Number Sensing Points:
One
Number Wires:
Two (Non-Polarity Sensitive)
Sensor Output @ 21.1ºC (70ºF):
1000 Ohms nominal
Lead Wire Colors:
Red/Red
Sensor Accuracy:
-40ºC (-40ºF): +/- 1.52ºC (+/- 2.73ºF) 0ºC (32ºF): +/- 0.4ºC (+/- 0.72ºF) 21.1ºC (70ºF): +/- 0.17ºC (+/- 0.34ºF) 54.4ºC (130ºF): +/- 0.56ºC (1.00ºF) 121ºC (250ºF): +/- 1.25ºC (+/- 2.25ºF)
Din Standard | Temperature Coeffcient:
Din 43760 | 6370 ppm/ºC
Nickel RTD Stability:
+/- 0.05% after 1000 Hours @ 150ºC (302ºF)
Response Time (63% Step Change):
8 Seconds nominal
Operating Temperature Range:
-40 to 115ºC (-40 to 239ºF)
Storage Temperature Range:
-40 to 85ºC (-40 to 185ºF)
Operating Humidity Range:
10 to 95% RH, non-condensing
Probe Material | Flange Material:
304 Stainless Steel | Galvanized Steel
Fitting Material | Flammability Rating:
Polyamide 66 (High Performance Nylon) | UL94-HB
Foam Pad Material | Flammability Rating:
Neoprene/EPDM/SBR Polymer | UL94-HBF; FMVSS-302; MIL-R-6130C
Lead Length | Conductor Size:
4”, 6” & 8” Probes: 14” (35.6 cm) | 12” & 18” Probes: 24” (61cm) | 22 AWG (0.65mm)
Lead Wire Insulation | Wire Rating:
Etched Teflon (PTFE) Colored Leads | MIL-W-16878/4 (Type E)
Conductor Material:
Silver Plated Copper
Probe Diameter:
0.250” (6.35mm)
Agency Approvals:
CE, RoHS2, WEEE